Description
The CX8090 is a control system with a switched Ethernet port. It supports protocols such as real-time Ethernet, ADS UDP/TCP, Modbus TCP client/server or open TCP/IP-UDP/IP communication. K-bus or E-bus terminals can be attached as required; the CX8090 automatically recognizes the type of I/O system connected during the start-up phase. The control system is programmed with TwinCAT via the fieldbus interface or the additional Ethernet interface.
| Technical data | CX8090 |
|---|---|
| Processor | ARM9, 400 MHz |
| Number of cores | 1 |
| Flash memory | 512 MB microSD (optionally expandable) |
| Main memory | 64 MB DDR2 RAM (not expandable) |
| Persistent memory | 1-second UPS (for 1 MB persistent data) |
| Programming languages | IEC 61131-3 |
| Web visualization | yes |
| Online change | yes |
| Up/down load code | yes/yes |
| Interfaces | 1 x RJ45 10/100 Mbit/s, 1 x USB device (behind the front flap), 1 x bus interface |
| Bus interface | 2 x RJ45 (switched) |
| Diagnostics LED | 1 x TC status, 1 x WD, 1 x error |
| Clock | internal battery-backed clock for time and date (battery behind the front flap, exchangeable) |
| Operating system | Windows Embedded CE 6 |
| Control software | TwinCAT 2 PLC |
| I/O connection | E-bus or K-bus, automatic recognition |
| Web-based management | yes |
| Current supply E-bus/K-bus | 2 A |
| Max. power consumption | 3 W |
| Dimensions (W x H x D) | 64 mm x 100 mm x 73 mm |
| Weight | approx. 180 g |
| Operating/storage temperature | 0…+55 °C/-25…+85 °C |
| Relative humidity | 95 %, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protection rating | IP20 |
| Approvals/markings | CE, UL, ATEX, IECEx, cFMus |
| Ex marking | ATEX: II 3 G Ex nA IIC T4 Gc II 3 D Ex tc IIIC T135 °C Dc IECEx: Ex nA IIC T4 Gc Ex tc IIIC T135 °C Dc cFMus: Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx ec IIC T4 Gc |
Data Sheet: cx8090






Reviews