CX8090

DIN rail Industrial PC  32 bit, 400 MHz CPU  256 MB microSD flash memory (optionally 1 GB, 2 GB or 4 GB) 64 MB

Internal main memory  protocol: real-time Ethernet

ModbusTCP, TCP/IP, UDP/IP, EtherCAT

Automation Protocol operating system: Microsoft Windows CE 6 programming: TwinCAT 2 PLC interfaces: 1 x Ethernet 10/100 Mbit/s (RJ 45), 1 x USB device

(behind the front flap)

bus interface: 2 x Ethernet RJ 45 (switched)

I/O connection: E-bus or K-bus Terminals

Categories: ,

Description

The CX8090 is a control system with a switched Ethernet port. It supports protocols such as real-time Ethernet, ADS UDP/TCP, Modbus TCP client/server or open TCP/IP-UDP/IP communication. K-bus or E-bus terminals can be attached as required; the CX8090 automatically recognizes the type of I/O system connected during the start-up phase. The control system is programmed with TwinCAT via the fieldbus interface or the additional Ethernet interface.

Technical data CX8090
Processor ARM9, 400 MHz
Number of cores 1
Flash memory 512 MB microSD (optionally expandable)
Main memory 64 MB DDR2 RAM (not expandable)
Persistent memory 1-second UPS (for 1 MB persistent data)
Programming languages IEC 61131-3
Web visualization yes
Online change yes
Up/down load code yes/yes
Interfaces 1 x RJ45 10/100 Mbit/s, 1 x USB device (behind the front flap), 1 x bus interface
Bus interface 2 x RJ45 (switched)
Diagnostics LED 1 x TC status, 1 x WD, 1 x error
Clock internal battery-backed clock for time and date (battery behind the front flap, exchangeable)
Operating system Windows Embedded CE 6
Control software TwinCAT 2 PLC
I/O connection E-bus or K-bus, automatic recognition
Web-based management yes
Current supply E-bus/K-bus 2 A
Max. power consumption 3 W
Dimensions (W x H x D) 64 mm x 100 mm x 73 mm
Weight approx. 180 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protection rating IP20
Approvals/markings CE, UL, ATEX, IECEx, cFMus
Ex marking ATEX:
II 3 G Ex nA IIC T4 Gc
II 3 D Ex tc IIIC T135 °C Dc
IECEx:
Ex nA IIC T4 Gc
Ex tc IIIC T135 °C Dc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc

Data Sheet: cx8090